Teledyne FLIR secures first UL 2684 listing for thermal fire detection

Teledyne FLIR secures first UL 2684 listing for thermal fire detection

Share this content

Facebook
Twitter
LinkedIn

Teledyne FLIR’s A40 and A70 thermal imaging cameras have become the first models listed under UL 2684, providing European fire engineers with independent evidence to support thermal fire detection specifications

Teledyne FLIR has announced that its A40 and A70 Axx-Series thermal imaging cameras are the first models to achieve listing under ANSI/CAN/UL 2684, the standard for video and thermal image detectors for fire alarm systems.

Although UL 2684 is a North American standard, the listing could support the specification and approval of thermal image fire detection systems in Europe, where radiometric thermal imaging is addressed through project-specific approval routes and national certification schemes.

These include VdS in Germany and CNPP in France. European regulatory requirements, CE marking obligations and applicable EN 54 standards continue to apply, with acceptance determined by the relevant approving authority.

Unlike conventional smoke, heat and flame detection technologies, radiometric thermal imaging monitors temperatures across a scene to identify abnormal heat conditions before smoke or flames develop.

EN 54-10 covers flame detection, including the flame-response capability of certified thermal cameras, while UL 2684 specifically evaluates video and thermal image detectors as fire detection devices.

In the US, the 2025 edition of NFPA 72, the National Fire Alarm and Signaling Code, introduced a dedicated category for thermal image fire detection under Section 17.12, requiring systems to be listed for fire detection.

Matthew Hasty, Global Vertical Director for Science, Automation, and Early Fire Detection at Teledyne FLIR, said: “Fire engineers work from evidence, and the strongest evidence is a published benchmark with an accredited laboratory behind it. That is what the listing adds for Europe. It gives the people building the technical case something independent to build on.”

The UL 2684 listing includes testing against defined fire scenarios involving flaming wood, flammable liquids and polyurethane, alongside environmental, electrical and durability assessments.

Teledyne FLIR said the listing provides fire engineers, risk professionals and consultants with an independent benchmark to support technical submissions, complementing manufacturer test data.

The company’s early fire detection solutions use radiometric thermal cameras to monitor defined regions of interest, measuring minimum, average and maximum temperatures. Alarm thresholds can be configured around absolute temperatures, differences between regions and rates of temperature rise.

The technology is designed for applications where developing heat conditions can indicate a potential fire risk, including waste and recycling facilities, manufacturing operations, battery energy storage installations, data centres and rooftop solar arrays.

Thermal imaging is line-of-sight, meaning cameras monitor specific areas or assets within their field of view. The systems are intended to complement conventional fire detection rather than replace it.

The Axx-Series cameras also combine thermal imaging with an integrated visible-light camera, providing video alongside alarms to help operators assess incidents and determine appropriate responses.

Teledyne FLIR said the UL 2684 listing provides additional independent evidence for European projects considering thermal image fire detection, while applicable national and project-specific approval requirements remain in place.

For more information about Axx-Series thermal imaging cameras and early fire detection solutions, visit Teledyne FLIR.

Newsletter
Receive the latest breaking news straight to your inbox